Int 0467-2024
Inspections of sprinkler system and standpipe system fire department connections.
IntroductionFiledCommittee on Fire and Emergency Managementintroduced 2024-02-28
Filed — closed without being enacted.
Official record · Legistar
Agenda: 2024-02-28Passed: 2025-12-31
Summary
This bill would require the New York City Fire Department (FDNY) to witness automatic sprinkler system and standpipe system tests every three years.
Committee on Fire and Emergency Management — Fire/EMS (non-health-related issues), and Emergency Management Department[ (OEM)].
How it compares
36% of similar bills passed
18 passed · 32 died
This bill: 672 days in committee
Similar bills: median 502 days · 124 days when passed
Compared against 50 Introduction bills in Committee on Fire and Emergency Management.
Ranked by how closely each matches this bill's topic — closest first:
Int 0133-2022
Inspections of sprinkler system and standpipe system fire department connections.
647dFiled
Int 0603-2018
Fire Safety Package - Requiring the fire department to meet certain standards for fire hydrant inspections and report on fire hydrant inspection results.
81dEnacted
Int 1841-2020
Requiring the FDNY to report on the dept’s fire alarm inspection unit.
723dFiled
Int 0088-2024
Qualifications of individuals to perform periodic inspection, test and maintenance fire and smoke dampers and smoke control systems.
691dFiled
Int 1054-2018
Creating online applications for fire alarm plan examinations and inspections.
110dEnacted
Int 1140-2024
Annual reporting on fire department vehicles and equipment.
363dEnacted
+ 44 more comparable bills
Sponsors (16)
Lifecycle
IntroducedIntroduced by Council
2024-02-28 · City Council
ActionReferred to Comm by Council
2024-02-28 · City Council
ClosedFiled (End of Session)
2025-12-31 · City Council
Heard at (1)
City Council · 2024-02-28 · 1:30 PM · Council Chambers - City Hall
Attachments (5)
- Summary of Int. No. 467
- Int. No. 467
- February 28, 2024 - Stated Meeting Agenda
- Hearing Transcript - Stated Meeting 2-28-24
- Minutes of the Stated Meeting - February 28, 2024
Full text
Be it enacted by the Council as follows:
Section 1. Subdivision 4 of section 903.5 of the New York city fire code is amended to read as follows:
4. Fire department connections shall be hydrostatically tested at least once every [5] 3 years, in accordance with FC912.6.
� 2. Subdivisions 4 and 5 of section 903.5.1 of the New York city fire code are amended to read as follows:
4. Fire department connections shall be hydrostatically tested at least once every [5] 3 years in accordance with FC912.6.
5. Upon order of the commissioner, but at least once every year, a flow test of the sprinkler system shall be conducted. Such test shall be conducted at the owner's risk by his or her representative, who shall be a licensed master plumber or licensed master fire suppression contractor. At least one such flow test shall be conducted before a representative of the department at least once every [5] 3 years. A report of each test, on an approved form, shall be certified by such licensed master plumber or licensed master fire suppression contractor and shall be kept for not less than 5 years and made available for inspection by any representative of the department.
� 3. Subdivisions 4 and 5 of section 903.5.2 of the New York city fire code are amended to read as follows:
4. Fire department connections shall be hydrostatically tested at least once every [5] 3 years in accordance with FC912.6.
5. Upon order of the commissioner, but at least once every year, a flow test of the sprinkler system shall be conducted; provided, however, that where there is a pressure gauge installed at or near the inspector's test location that is checked during the required monthly inspection described in FC903.5.2(1) to make certain the system design pressure is being maintained, a flow test of the sprinkler system shall be conducted upon order of the commissioner, but at least once every 30 months. Such test shall be conducted at the owner's risk by his or her representative, who shall be a plumber or licensed master fire suppression contractor. At least one such test shall be conducted before a representative of the department at least once every [5] 3 years. A report of each test, on a form prepared by the department, shall be certified by such plumber or licensed master fire suppression contractor and shall be kept for not less than 5 years and made available for inspection by any representative of the department.
� 4. Section 905.2.1 of the New York city fire code, as amended by local law number 148 for the year 2013, is amended to read as follows:
905.2.1. Standpipe hydrostatic pressure and flow tests. Upon order of the commissioner, but at least once every [5] 3 years, the standpipe system shall be subjected to a hydrostatic pressure test and a flow test to demonstrate its suitability for department use. These tests shall be conducted in compliance with the requirements of the rules and shall be conducted at the owner's risk, by his or her representative before a representative of the department.
� 5. Section 912.6 of the New York city fire code, as amended by local law number 148 for the year 2013, is amended to read as follows:
912.6. Maintenance. Sprinkler system and standpipe system fire department connections shall be periodically inspected, tested, serviced and otherwise maintained in accordance with FC901.6 and NFPA 25. Upon order of the commissioner, but at least once every [5] 3 years, such fire department connections shall be subjected to a hydrostatic pressure test to demonstrate their suitability for department use. The test shall be conducted in accordance with the rules and at the owner's risk, by his or her representative before a representative of the department.
� 6. This local law takes effect immediately.