Int 0462-2006
Requiring radio repeaters in high-rise buildings.
IntroductionFiledCommittee on Fire and Criminal Justice Servicesintroduced 2006-10-25
Filed — closed without being enacted.
Official record · Legistar
Agenda: 2006-10-25Passed: 2009-12-31
Committee on Fire and Criminal Justice Services — Fire/EMS (non-health-related issues), Department of Probation, Department of Correction, and Emergency Management Department (OEM).
How it compares
20% of similar bills passed
10 passed · 40 died
This bill: 1163 days in committee
Similar bills: median 381 days · 90 days when passed
Compared against 50 Introduction bills in Committee on Fire and Criminal Justice Services.
Ranked by how closely each matches this bill's topic — closest first:
Int 0698-2015
Designating communications havens for emergency events.
1038dFiled
Int 0905-2008
Requiring the Fire Commissioner to maintain a Fire Communication Centers in every Borough.
377dFiled
Int 0745-2008
Appointment and duties of the citywide high-rise firefighting commission.
624dFiled
Int 0249-2004
In relation to overcrowding.
660dFiled
Int 0482-2006
Radio communication between the NYPD and EMS and those that provide emergency medical service under the Fire Department’s 911 dispatch system.
1128dFiled
Int 0295-2004
Fire safety in places of public assembly
614dEnacted
+ 44 more comparable bills
Sponsors (8)
Lifecycle
IntroducedIntroduced by Council
2006-10-25 · City Council
ActionReferred to Comm by Council
2006-10-25 · City Council
ClosedFiled (End of Session)
2009-12-31 · City Council
Heard at (1)
City Council · 2006-10-25 · 1:30 PM · Council Chambers - City Hall
Full text
Be it enacted by the Council as follows:
Section 1. Chapter 4 of title 27 of the administrative code of the city of New York is amended by adding a new subchapter 30, to read as follows:
Subchapter 30
High Rise Building Radio Repeaters
§27-4301 Definitions.
§27-4302 Amplification System Required.
§27-4303 Acceptance Test Procedures.
§27-4304 Annual Tests.
§27-4305 Qualifications of Testing Personnel.
§27-4306 Fire Department Inspections.
§27-4307 Additional Requirements.
§27-4308 Violations.
§27-4301 Definitions. For purposes of this subchapter, the following terms shall have the following meanings:
a. “high rise building” means; all new and existing buildings classified in occupancy groups, C, E, G, J-1 and J-2 that are seventy-five feet or more in height.
b. “adequate radio coverage” means; a clearly audible transmission available in 100% of the area of each floor of a high rise building when transmitted from one standard issue New York City Fire Department portable radio to another standard issue New York City Fire Department portable radio from 100% of the area of each floor of the high rise building.
c. “high rise building radio repeater system” or “system” means; a technological system that promotes radio communications without degredation throughout a high rise building, the specifications of which shall be determined and approved by the New York City Fire Department.
d. “acceptance test” means; dividing each floor of the high rise building into a grid of approximately forty equal areas and establishing a location on the first floor in the center of a grid to act as a command post. Radio calls must then be made from the command post via a standard issue New York City Fire Department portable radio to another standard issue New York City Fire Department portable radio located in the center point of each of the remaining grids on the first floor and to the center of each of the forty grids on each floor in the remainder of the building. Return radio calls must also be made from each of these locations to the command post. Each of these radio calls must result in a clearly audible transmission.
§27-4302. High Rise Building Radio Repeater System Required. Within twelve months of the enactment of this subchapter, any person who owns a high rise building covered by this subchapter shall be required to install a high rise building radio repeater system, capable of providing adequate radio coverage, subject to the approval and testing of the Commissioner of the New York City Fire Department. A Certificate of Occupancy will not be issued to any high rise building if the high rise building fails to comply with this subchapter.
§27-4303. Acceptance Test Procedures. Acceptance testing for a high rise building radio repeater system is required upon completion of installation and annually thereafter. Acceptance testing shall be overseen by a representative of the New York City Fire Department. Such testing is the responsibility of the building owner. The results of those tests shall be documented in a form acceptable to the Commissioner of the New York City Fire Department and a hard copy kept on file with the building owner.
§27-4304. Annual Tests. When a high rise building radio repeater system is installed, the building owner shall test all active components of the system a minimum of once every twelve (12) months to determine whether or not such components are operating within the manufacturer’s specifications for the intended purpose.
§27-4305. Qualifications of Testing Personnel. All tests shall be conducted, documented, and signed by a person in possession of a current FCC General Radio Telephone Operator License. A hard copy of all test records shall be submitted to the New York City Fire Department by the building owner.
§27-4306. Fire Department Inspections. Fire Department Radio personnel, after providing reasonable notice to the building owner or his representative, shall have the right to enter the building to conduct field inspections to be certain that adequate radio coverage is present.
§27-4307. Additional Requirements. a. The building owner shall be responsible for making any upgrades to the system required by the Commissioner of the New York City Fire Department in order to achieve adequate radio coverage. b. The building owner shall be responsible for having a maintenance contract for the system in place that provides for a 24 hour by 7 day emergency response within two (2) hours after notification and must provide the name and phone number of the maintenance contractor to the Commissioner.
§27-4308 Violations. Any person who shall violate the provisions of sections 27-4302, 4303 of this subchapter, shall, upon conviction thereof, be liable for a civil penalty of not less than ten thousand dollars nor more than twenty five thousand for the first offense and a penalty of not less than twenty five thousand dollars nor more than fifty thousand dollars for each succeeding such violation. For the purposes of this section, no more than one violation of this subchapter may be issued on the same business day.
§2. Effect of invalidity; severability. If any section, subsection, sentence, clause, phrase, or other portion of this local law is, for any reason, declared unconstitutional or invalid, in whole or in part, by any court of competent jurisdiction, such portion shall be deemed severable, and such unconstitutionality or invalidity shall not affect the validity of the remaining portions of this local law, which remaining portions shall continue in full force and effect.
§3. This local law shall take effect ninety days after its enactment provided, however, the commissioner may take any actions necessary prior to such effective date for the implementation of this local law including, but not limited to, the adoption of any necessary rules.
RCC
LS 791